产品展示

Rosemount 248 Temperature transmitter with HART protocol

作者:admin 发布日期:2011-4-18 3:17:29点击:1558

Rosemount 248 Temperature transmitter with HART protocol 

A complete temperature assembly for any Single Point measurement application

The Rosemount 248 Temperature Transmitter is designed to meet common Single Point measurement application requirements.  This transmitter with HART® protocol can easily be ordered with a variety of sensors (RTDs and thermocouples) and thermowells.   The Rosemount 248 is provided in a head mount configuration suitable for installation in a wide variety of connection heads and housings.  Additionally, a Rail Mount configuration is also available for rail and rack mountable applications.  A PC-programmable interface is available, providing an easy-to-use configuration method from any PC.


Features & Benefits

Ready to Install. Remove it from the Box and Install into the Process for significant cost savings

Unsurpassed Performance for Temperature Monitoring Points

Industry Standard DIN Form B Size Enables Mounting in Any Connection Head

Reliable EMC Performance by Meeting NAMUR NE 21

Recommendation Communicates Using Open HART / 4-20 mA Protocol

Specifications

Key Specifications
Digital Accuracy0.20°C (0.36°F) or 0.1% of span
Ambient Temperature Effect± 0.006°C/°C per 1.0°C (1.8°F) change in ambient (Pt100 RTD)
Stability0.1% reading or 0.1°C (0.18°F) for 1 year
Input2-, 3-, and 4-wire RTDs, thermocouple, millivolt, ohm
Output  2-wire, linear with temperature or input on 4-20 mA/HART signal
Supply Voltage12 - 42.2V
Supply Voltage12 - 42.2V in HART Protocol
9 - 32V in FOUNDATION Fieldbus Protocol